TKDW2 series Air circuit-breaker (ACB)

TKDW2 series intelligent Air Circuit Breaker (ACB) (hereinafter referred to as Circuit-breaker) is suitable for AC 50Hz, Rated voltage up to AC800V, rated insulation voltage 1000V, and Rated working current 6300A and below distribution networks, used for power distribution and protecting circuits, power equipment, etc., from hazards such as overload, undervoltage, short circuit, and single-phase grounding faults. The Circuit-breaker can be equipped with various intelligent controllers, offering complete protection functions.

Belonging Category:

Keywords:

TKDW2 series Air circuit-breaker (ACB)

Product Details

Application Range

The TKDW2 series intelligent Air Circuit Breaker (ACB) (hereinafter referred to as Circuit-breaker) is suitable for AC 50Hz, rated voltage up to AC 800V, rated insulation voltage 1000V, rated working current 6300A and below distribution networks, used for power distribution and protecting circuits and power equipment from damage caused by overloads, undervoltages, short circuits, and single-phase grounding faults. The Circuit-breaker can be equipped with various intelligent controllers, providing comprehensive protection functions.

The Circuit-breaker has isolation function:

Compliant with "Technical Specifications for Low-Voltage AC Grid-Side Circuit Breakers", suitable for harsh environments such as high temperature, low temperature, salt spray, and humidity, meeting the requirements of photovoltaic and wind power systems.

Standards and Certifications

GB/T 14048.1 Low-voltage switchgear and controlgear Part 1: General rules

GB/T 14048.2 Low-voltage switchgear and controlgear Part 2: Circuit-breakers

GB/T 14048.4 Low-voltage switchgear and controlgear Part 4-1: Contactors and motor starters Electromechanical contactors and motor starters (including motor protectors)

GB/T 20645 Technical requirements for low-voltage electrical appliances for use in high-altitude special environments

GB/T 2423.1 Environmental testing of electrical and electronic products Part 2: Test methods Test A: Low temperature

GB/T 2423.2 Environmental testing of electrical and electronic products Part 2: Test methods Test B:   High temperature

GB/T 2423.4 Environmental testing of electrical and electronic products Part 2: Test methods Test Db: Damp heat, cyclic

GB/T 2423.17 Environmental testing of electrical and electronic products Part 2: Test methods Test Ka: Salt mist

GB/T 2423.18 Environmental testing of electrical and electronic products Part 2: Test methods Test Kb: Salt mist, cyclic

Stand working conditions

Applicable ambient temperature -40°C~+70°C, the average value of 24h does not exceed +35°C;

The altitude of the installation location does not exceed 5000m;

When the highest temperature is +40°C, the relative humidity of the air does not exceed 50%, and higher relative humidity is allowed at lower temperatures, for example, 90% at 20°C. Special measures should be taken for occasional condensation due to temperature changes;

Pollution degree: Grade 3;

The Circuit-breaker is installed in an indoor cabinet with a door frame, and the protection level is IP40;

Usage category: B;

The installation category for the Circuit-breaker power circuit and primary coil of the power transformer is IV; the installation category for other auxiliary circuits and control circuits is III;

The vertical inclination of the installation does not exceed 5°;

Transportation and storage conditions: Not lower than -40°C, not higher than 70°C;

Circuit-breaker
Connection Method
TKDW1 seriesTKDW2 seriesTKDW3 series
16006300N2H1HU1H2HU2H3HU3
Horizontal connection
Vertical connection----
Forward connection------
Horizontal and vertical connection----
Vertical and horizontal connection----
Forward and horizontal connection------
Horizontal and forward connection------
Vertical and forward connection------
Forward and vertical connection------
Note: ● indicates standard connection method, ○ indicates optional connection method, - indicates no such connection method
ModelTKDW2-6300TKDW2-1600
Rated working current In (A)4000 5000 6300200, 400, 630, 800, 1000, 1250, 1600
Rated voltage Ue (V) 50HzAC400VAC690VAC800VAC400V
Rated insulation voltage Ui (V)10001000
Rated impulse withstand voltage Uimp (kV)1212
Power frequency withstand voltage U (V) 1minAC5000V 50HzAC5000V 50Hz
Pole number3P/4P3P/4P
Rated ultimate breaking capacity (rms) Icu (kA)130856555
Rated operating breaking capacity (rms) Ics (kA)100856550
Rated short-circuit making capacity (peak) Icm (kA)286187143121
Rated short-circuit withstand current (rms) Icw (kA) 1s100856550
Total breaking time (without additional delay) (ms)≤3012~18
Closing time (ms)≤70≤60
Mechanical PerformanceMechanical life500200-800A: 10000 times
1000-1600A: 6500 times
Mechanical lifeMaintenance-free400010000
With maintenance800020000
Normal operating conditionsUsage categoryBB
Pollution degreeGrade 2Grade 3
Protection LevelIP40IP40
Ambient TemperatureNo less than -40℃No less than -40℃
Altitude≤5000m≤5000m
Dimensions (mm) (H×W×D)Drawer-type 3P4000A-5000A: Offset type
402×800×504

6300A: Offset type

433x928×504

4000A-6300A: Center type

437×895×470

353×279×300
Drawer-type 4P402×915×504433×928×504437×895x470353×359×300
Fixed type 3P433×813×504402×915×504402×882×445330×297×202
Fixed type 4P433×928×504402×915×504402×882x445330×377×202

 