TKDW1 series Air circuit-breaker (ACB)

The TKDW1 series intelligent Air Circuit Breaker (ACB) (hereinafter referred to as Circuit-breaker) is suitable for AC 50Hz distribution networks with a rated voltage up to AC690V, rated insulation voltage of 1000V, and rated working current of 4000A or less. It is used to distribute power and protect circuits and power equipment from damage caused by overloads, undervoltages, short circuits, and single-phase grounding faults. The Circuit-breaker can be equipped with a variety of intelligent controllers, providing comprehensive protection functions.

Belonging Category:

Keywords:

TKDW1 series Air circuit-breaker (ACB)

Product Details

Application Range

The TKDW1 series intelligent Air Circuit Breaker (ACB) (hereinafter referred to as Circuit-breaker) is suitable for AC 50Hz, rated voltage up to AC690V, rated insulation voltage 1000V, rated working current 4000A and below power distribution networks. It is used to distribute power and protect circuits and power equipment from damage caused by overloads, undervoltages, short circuits, and single-phase grounding faults. The Circuit-breaker can be equipped with various intelligent controllers, providing comprehensive protection functions.

The Circuit-breaker has an isolation function:

Compliant with the "Technical Specifications for Low-Voltage AC Grid-Connected Circuit Breakers", suitable for harsh environments such as high temperature, low temperature, salt spray, and humidity, meeting the requirements of photovoltaic and wind power systems.

Standards and Certifications

GB/T 14048.1 Low-voltage switchgear and controlgear Part 1: General rules

GB/T 14048.2 Low-voltage switchgear and controlgear Part 2: Circuit-breakers

GB/T 14048.4 Low-voltage switchgear and controlgear Part 4-1: Contactors and motor starters Electromechanical contactors and motor starters (including motor protectors)

GB/T 20645 Technical requirements for low-voltage electrical appliances for use in special environmental conditions at high altitudes

GB/T 2423.1 Electrical and electronic products Environmental testing Part 2: Test methods Test A: Low temperature

GB/T 2423.2 Electrical and electronic products Environmental testing Part 2: Test methods Test B: High temperature

GB/T 2423.4 Electrical and electronic products Environmental testing Part 2: Test methods Test Db: Damp heat, cyclic

GB/T 2423.17 Electrical and electronic products Environmental testing Part 2: Test methods Test Ka: Salt mist

GB/T 2423.18 Electrical and electronic products Environmental testing Part 2: Test methods Test Kb: Salt mist, cyclic

Stand working conditions

Applicable ambient temperature -40°C~+70°C, the 24h average value does not exceed +35°C;

The altitude of the installation location does not exceed 5000m;

When the highest temperature is +40°C, the relative humidity of the air does not exceed 50%. At lower temperatures, higher relative humidity is allowed, for example, 90% at 20°C. Special measures should be taken for occasional condensation due to temperature changes;

Pollution degree: Grade 3;

The Circuit-breaker is installed in a cabinet and equipped with a door frame, with a protection level of IP40;

Usage category: B;

The installation category of the Circuit-breaker main circuit and the primary coil of the power transformer is IV; the installation category of other auxiliary circuits and control circuits is III;

The vertical inclination of the installation does not exceed 5°;

Transportation and storage conditions: Not lower than -40°C, not higher than 70°C;

Circuit-breaker
Connection Method
TKDW1 SeriesTKDW2 SeriesTKDW3 Series
16006300N2H1HU1H2HU2H3HU3
Horizontal Connection
Vertical Connection----
Forward Connection------
Horizontal and Vertical Connection----
Vertical and Horizontal Connection----
Forward and Horizontal Connection------
Horizontal and Forward Connection------
Vertical and Forward Connection------
Forward and Vertical Connection------
Note: ● indicates standard connection method, ○ indicates optional connection method, - indicates no such connection method
ModelTKDW1-2000TKDW1-3200TKDW1-4000
Rated working current In(A)200 400 600 800 1000 1250 1600 20002000 2500 2900 32003200 3600 4000
Rated voltage Ue(V)50HzAC400VAC550VAC690VAC400VAC690VAC400V
Rated insulation voltage Ui(V)100010001000
Rated impulse withstand voltage Uimp(kV)121212
Power frequency withstand voltage U(V)1minAC5000V 50HzAC5000V 50HzAC5000V 50Hz
Pole number3P/4P3P/4P3P/4P
Rated ultimate breaking capacity(RMS)Icu(kA)80656510075100
Rated operating breaking capacity(RMS)Ics(kA)656565807580
Rated short-circuit making capacity(peak)Icm(kA)176143143220165220
Rated short-circuit withstand current(RMS)Icw(kA)1s656565807580
Total breaking time (without additional delay) (ms)≤30≤30≤30
Closing time (ms)≤70≤70≤70
Mechanical PropertiesMechanical life65003000300015001500
Mechanical lifeMaintenance-free150001500010000
With maintenance300003000020000
Normal operating conditionsUsage categoryBBB
Pollution degreeGrade 3Grade 3Grade 3
Protection levelIP40IP40IP40
Ambient temperatureNot lower than -40℃Not lower than -40℃Not lower than -40℃
Altitude≤5000m≤5000m≤5000m
Dimensions (mm) (H×W×D)Drawer type 3P433×375×452433×435×470433×550×487-
Drawer-type 4P433×470×452433×550×470-433×788×504
Fixed-type 3P402×362×360402×422×368402×537×368-
Fixed-type 4P402×457×360402×537×368-402×772×360

 

 