TKDM1L series circuit breaker with residual current protection
Belonging Category:
Keywords:
TKDM1L series circuit breaker with residual current protection
Product Details
Scope of Application and Main Features
The TKDM1L series circuit breaker with residual current protection (hereinafter referred to as circuit breaker) is suitable for AC 50Hz, rated insulation voltage 1000V, rated voltage 400V, and rated current up to 630A distribution networks for infrequent switching and infrequent motor starting. The circuit breaker has overload, short-circuit, undervoltage, and residual current protection functions, which can protect the lines and power equipment from damage, and also provide protection against ground faults and indirect contact in the circuit.
This series of circuit breakers features compact structure, small size, high breaking capacity, and complete internal and external accessories.
This series of circuit breakers has an isolation function, and its corresponding symbol is:
This series of circuit breakers has complete residual current protection functions, including time-delay type, non-time-delay type, and electrical alarm type.
Standards Compliance
IEC 60947-1 and GB/T 14048.1 Low-voltage switchgear and controlgear General rules
IEC 60947-2 and GB/T 14048.2 Low-voltage switchgear and controlgear Circuit-breakers
IEC 60947-4-1 and GB/T 14048.4 Low-voltage switchgear and controlgear Electromechanical contactors and motor starters
IEC 60947-5-1 and GB/T 14048.5 Low-voltage switchgear and controlgear Electromechanical control circuit electric appliances
Operating and Installation Conditions
The ambient air temperature should not exceed +40℃, and the average temperature over 24 hours should not exceed +35℃. The lower limit of the ambient air temperature is -5℃. Note: For operating conditions where the ambient air temperature is higher than +40℃ or lower than -5℃, users should consult the manufacturer;
The altitude of the installation location should not exceed 2000m;
When the highest temperature is +40℃, the relative humidity of the air should not exceed 50%. Higher relative humidity is allowed at lower temperatures, for example, 90% at 20℃. Special measures should be taken for condensation occasionally caused by temperature changes;
In places where there is no explosive medium in the air and no gases and conductive dust that can corrode metals and damage insulation;
In places free from rain and snow;
Pollution degree is level 3;
The maximum inclination angle for circuit breaker installation is ±22.5°;
Installation category: The installation category of the main circuit of the circuit breaker is Ⅲ, and the installation category of the auxiliary circuit and control circuit not connected to the main circuit is Ⅱ;
The circuit breaker should be installed and used according to the product manual requirements; Note: The TKDM1L series residual current circuit breaker is generally top-in and bottom-out (i.e., 1, 3, 5 are the power terminals, and 2, 4, 6 are the load terminals). If the user needs a reverse-in type product, it should be specified when ordering;
Protection level IP30;
TKD 1 |
M 2 |
1 3 |
L 4 |
250 5 |
P 6 |
4 8 |
300 9 |
A 10 |
丄 11 |
□ 12 |
Serial Number | Description | Model Meaning |
---|---|---|
1 | Enterprise code | TKD: Shandong Taikai Electrical Appliance Co., Ltd. |
2 | Product Category | M: Moulded-case circuit-breaker (MCCB) |
3 | Design SN | 1 |
4 | Function Code | L: With residual current protection |
5 | Frame Size | 100、125、225、250、400、630 |
6 | Operation Mode Code | No code: Direct handle operation P: Electric operating mechanism Z: Rotary handle operating mechanism |
7 | Pole Number | 3: 3 poles 4: 4 poles |
8 | Internal Accessory Code | 300: No accessories Others see Trip method and internal accessories table |
9 | Neutral Pole Form | Neutral pole (N pole) form in four-pole circuit breaker: Type A, Type B, Type C, Type D ① |
10 | Leakage Current Alarm Module | Blank: Standard configuration I: Alarm trip, II: Alarm no trip |
11 | Cabling Type | Blank: Front panel wiring Optional: Plug-in front panel wiring, plug-in rear panel wiring, connecting block |
Note:
①Neutral pole code explanation:
A: No overcurrent trip unit is installed on the N pole, and the N pole is always connected, not switched with the other three poles;
B: No overcurrent trip unit is installed on the N pole, and the N pole is switched with the other three poles (N pole closes later and opens later);
C: An overcurrent trip unit is installed on the N pole, and the N pole is switched with the other three poles (N pole closes later and opens later);
D: An overcurrent trip unit is installed on the N pole, and the N pole is always connected, not switched with the other three poles;
Technical Performance Indicators
Frame Size Rated Current (A) | 100/125 | 225/250 | 400 | 630 | |||||||
---|---|---|---|---|---|---|---|---|---|---|---|
Model | TKDM1L-100 TKDM1L-125 |
TKDM1L-225 TKDM1L-250 |
TKDM1L-400 | TKDM1L-630 | |||||||
Rated currentIn (A) | 16, 20, 25, 32, 40, 50, 63, 80, 100, 125 | 100, 125, 140, 160, 180, 200, 225, 250 | 225, 250, 315, 350, 400 | 400, 500, 630 | |||||||
Pole Number | 2 | 3 | 4 | 2 | 3 | 4 | 3 | 4 | 3 | 4 | |
Rated insulation voltage Ui (V) | AC 1000V | ||||||||||
Rated impulse withstand voltage Uimp (V) | 8000 | ||||||||||
Rated voltage Ue (V) | AC400 | ||||||||||
Arcing distance (mm) | >50 | >100 | |||||||||
Rated ultimate breaking capacity Icu (kA) | AC400V | 50 | 50 | 65 | 65 | ||||||
Rated operating breaking capacity Ics (kA) | AC400V | 35 | 35 | 42 | 42 | ||||||
Rated residual operating current I·n (mA) | Non-delayed | 30/100/500 | 100/300/500 | 100/300/500 | 300/500/1000 | ||||||
Non-delayed, adjustable delay | 100/300/500 | 100/300/500 | 100/300/500 | 300/500/1000 | |||||||
Rated residual non-operating current I·no (mA) | 1/2I·n | ||||||||||
Rated residual short-circuit closing (breaking) capacity I·m (kA) | 1/4Icu | ||||||||||
Mechanical life (times) * | 8000 | 8000 | 7500 | 7500 | |||||||
Mechanical life (times) * | Maintenance-free | 20000 | 20000 | 10000 | 10000 | ||||||
Requires maintenance | 40000 | 40000 | 20000 | 20000 | |||||||
Neutral (N) Rated current | Same as Circuit-breaker Rated current |
★According to GB/T 14048.1, the term "life" refers to the probability of the number of operations that an electrical appliance can complete before repair or replacement of parts.
★In TKDM1L-125 enclosure, Rated current is only 125A; in TKDM1L-250 enclosure, Rated current is only 250A.
★TKDM1L-125 enclosure and TKDM1L-225 enclosure have 2P products; other enclosures do not have 2P products.
Related Products
Product Inquiry
You can leave your opinions and suggestions here, and we will reply to you in time
SHANDONG TAIKAI ELECTRIC APPLIANCES CO., LTD.
Service Hotline:
86-538-8520889
Tel:
86-538-8520889(Sales and Marketing Support)
86-538-5366875(General Department, Human Resources Department)
Email:tkdgdq@163.com
Address: No.11 Leigushi East Street,Taishan District,TaiAnCity, Shandong Province

WeChat Official Account
copyright © 2025 ShanDong TaiKai Electric Appliances Co., Ltd.