TKDQ1 series automatic transfer switch

The TKDQ1 series automatic transfer switch is suitable for two-way power supply systems with a rated voltage of AC400V and a frequency of 50Hz, and a rated working current of up to 800A. It serves as a switching device between the normal power supply and the backup power supply. When one power supply fails, it automatically switches between the normal and backup power supplies to ensure the continuity of power supply to important equipment, while also providing short-circuit and overload protection for the downstream load and cables. It is mainly used in important places such as hospitals, shopping malls, banks, and fire protection where power outages are not allowed.

Keywords:

TKDQ1 series automatic transfer switch

Product Details

Scope of Application

The TKDQ1 series automatic transfer switch is suitable for two-way power supply systems with a rated voltage of AC400V, a frequency of 50Hz, and a rated working current of up to 800A. It serves as a switching device between the normal and backup power supplies. When one power supply fails, it automatically switches between the normal and backup power supplies to ensure the continuity of power supply to important equipment, while also providing short-circuit and overload protection to the downstream load and cables. It is mainly used in important places such as hospitals, shopping malls, banks, and fire protection where power outages are not allowed.

Standards Compliance

IEC60947-1 GB/T 14048.1 Low-voltage switchgear and controlgear General rules

IEC60947-2 GB/T 14048.2 Low-voltage switchgear and controlgear Circuit-breaker

IEC60947-6-1 GB/T 14048.11 Low-voltage switchgear and controlgear Multifunctional appliances Switching appliances

Operating and Installation Conditions

The ambient air temperature should not exceed +40℃, and the 24-hour average should not exceed +35℃. The lower limit of the ambient air temperature is -5℃; Note: For operating conditions where the ambient air temperature is higher than +40℃ or lower than -5℃, users should consult with our company;

The installation altitude should not exceed 2000m;

When the highest temperature is +40℃, the relative humidity of the air should not exceed 50%. Higher relative humidity is allowed at lower temperatures, for example, 90% at 20℃. Special measures should be taken for occasional condensation due to temperature changes;

The installation location should be free from explosive media in the air and free from gases and conductive dust that can corrode metals and damage insulation; no rain or snow;

Pollution degree is level 3;

The maximum inclination of the circuit-breaker installation is ±22.5°;

Installation category: The installation category of the main circuit of the circuit-breaker is III, and the installation category of the auxiliary circuit and control circuit not connected to the main circuit is II;

The circuit-breaker should be installed and used according to the requirements of the product manual;

Product Structural Features

The TKDQ1 series dual-power automatic transfer switch consists of two TKDM series Moulded-case circuit-breakers (MCCBs) (three-pole or four-pole), their accessories, a mechanical interlocking transmission mechanism, an intelligent controller, etc. The product is available in integral and split structures.

Its features are:

There is a reliable mechanical interlocking device and electrical interlocking protection between the two circuit-breakers, eliminating the possibility of both circuit-breakers closing at the same time;

It has short-circuit and overload protection functions, as well as overvoltage, undervoltage, and phase-loss automatic transfer functions;

The intelligent controller uses a single-chip microcomputer for control, with a simple design, complete functions, and high reliability;

The controller circuit design adopts power sampling and single-chip microcomputer control separation, eliminating electromagnetic interference from the structural design;

The controller of the integral automatic transfer switch can be removed and installed on the switchgear panel for split installation, only needing to connect the controller and the main unit with a 2-meter-long signal cable;

The transfer switch has three different control functions: self-starting and self-restoring (R), self-starting but not self-restoring (S), and grid-generator (F), suitable for grid-grid power distribution systems and grid-generator power distribution systems, respectively;

Protection parameters such as switch transfer delay time and over/undervoltage protection action values can be freely set externally to meet the requirements of different locations;

Model and Meaning

TKD
1
Q
2
1  
3
- 250  
4
/ 3P
5
250A
6
R
7
Integral
8

9
Serial Number Description Model Meaning
1 Enterprise code TKD: Shandong Taikai Electrical Appliance Co., Ltd.
2 Product Category Q: Automatic Transfer Switch
3 Design SN 1: The actuator switch is a Moulded-case circuit-breaker (MCCB)
4 frame size 63、125、250、400、630、800
5 Pole number 3P、4P
6 Rated current See the main technical parameters table
7 Controller Function Code R: Self-starting and self-restoring, S: Self-starting but not self-restoring, F: Grid to generator
8 Product Structure Integral, Split
9 Optional Functions See the main technical parameters table

  Main Technical Parameters

Specifications and Models TKDQ1-63 TKDQ1-125 TKDQ1-250 TKDQ1-400 TKDQ1-630 TKDQ1-800
Rated voltage Ue(V) AC400V 50Hz
Rated current Ie(A) 16、20、25、32、40、50、63 16、20、25、32、40、50、63、80、100、125 100、125、140、160、180、200、225、250 225、250、315、350、400 400、500、630 630、700、800
Rated insulation voltage Ui(V) 690
Pole number 3P、4P
Rated short-circuit breaking capacity Icn (kA) 35 35/50 35/50 50/65 50/65 50/65
Mechanical life (cycles) 3000 3000 3000 2000 1500 1500
Mechanical life (cycles) 6000 6000 6000 4000 2500 2500
Manual switching Yes
Automatic switching Yes
Product Structure Integral, Split
Switching delay (s) 0-180s adjustable
Return delay (s) 0-180s adjustable
Voltage detection function Overvoltage, undervoltage, phase loss
Overvoltage detection value 240-290V adjustable
Undervoltage detection value 160-200V adjustable
Controller operating power supply AC150-300V 50/60Hz
Display method Chinese digital tube display
Voltage display function Yes
Generator control One set of 10A relay dry contacts
Fire linkage control Passive contact input, with one set of normally open passive signal feedback contacts
Overload, short circuit protection Yes
Communication interface RS 485 (optional)

Product Inquiry

You can leave your opinions and suggestions here, and we will reply to you in time