TKDC3 series AC contactors

The TKDC3 series AC contactors (hereinafter referred to as contactors) are mainly used in AC 50Hz or 60Hz power systems with a rated insulation voltage of 690V and a rated working current of up to 630A to connect and disconnect circuits. They can be combined with appropriate thermal overload relays to protect circuits that may be overloaded. The contactors are suitable for frequently starting and controlling AC motors.

Belonging Category:

Keywords:

TKDC3 series AC contactors

Product Details

Scope of application

The TKDC3 series AC contactors (hereinafter referred to as contactors) are mainly used in AC 50Hz or 60Hz power systems with a rated insulation voltage of 690V and a rated working current of up to 630A to connect and disconnect circuits. They can be combined with appropriate thermal overload relays to protect circuits that may be overloaded. The contactors are suitable for frequent starting and control of AC motors.

Standards Compliance

The TKDC3 series AC contactors comply with the following standards:

IEC 60947-4-1:2009 and GB/T 14048.4-2010 Low-voltage switchgear and controlgear - Electromechanical contactors and motor starters

Operating and Installation Conditions

Ambient air temperature: -5℃~+40℃; and the 24h average value does not exceed +35°C;

The altitude of the installation location does not exceed 2000m;

At +40℃, the relative humidity of the atmosphere does not exceed 50%; at lower temperatures, higher relative humidity is allowed. The monthly average minimum temperature of the wettest month does not exceed 25℃, and the monthly average maximum relative humidity of that month does not exceed 90%. Measures must be taken for condensation on the product due to temperature changes;

Pollution degree: Grade 3;

Installation category: Category Ⅲ;

Installation conditions: The inclination of the mounting surface to the vertical surface is not more than +5°;

Impact and vibration: The product should be installed and used in places without significant shaking, impact, and vibration;

Structural Features

Modular design: Auxiliary contact groups, air delay heads, thermal relays, and other accessories are modularly designed and can be combined into various derivative products;

Small size, low power consumption, long life, and reliable safety;

It can be installed with screws or standard DIN rail;

Model and Meaning

TKD
1
C
2
3   
3
- D
4
09   
5
11   
6
F4
7
LA
8
Serial Number Description Model Meaning
1 Enterprise code TKD:Shandong Taikai Electrical Appliance Co., Ltd.
2 Product Category C: AC Contactor
3 Design SN 3
4 Transparent cover code D: Indicates with dustproof transparent cover, without dustproof transparent cover
09A~95A can be equipped with a transparent cover, 95A and above cannot be equipped with a transparent cover
5 Basic current specification 09~630 uses 400V(380V), AC-3 Rated working current value
6 Type and quantity of built-in auxiliary contacts Contactors with 32A and below have one pair of normally open or normally closed auxiliary contacts. 40A~95A have one pair of normally open and normally closed auxiliary contacts. Products with 115A and above do not have built-in auxiliary contacts; "10" indicates one normally open auxiliary contact, "01" indicates one normally closed auxiliary contact (≤32A); "11" indicates one normally open and one normally closed auxiliary contact (40A~95A). For reversible contactors, this refers to the type and quantity of contacts per unit.
7 External auxiliary contact accessories F4: Indicates front mounting, F8 indicates side mounting (see page 7-04 for external auxiliary contact selection guide)
8 Air delay head accessories LA: Indicates air delay head accessories (see page 7-05 for air delay head accessories guide)

Operating and Installation Conditions   

● Ambient air temperature: -5°℃~+40°C; and the 24h average value does not exceed +35℃.

● The altitude of the installation location does not exceed 2000m;

● At +40℃, the relative humidity of the atmosphere does not exceed 50%; at lower temperatures, higher relative humidity is allowed. The monthly average minimum temperature of the wettest month does not exceed 25℃, and the monthly average maximum relative humidity of that month does not exceed 90%. Measures must be taken for condensation on the product due to temperature changes;

● Pollution degree: Grade 3;

● Installation category: Category Ⅲ;

● Installation conditions: The inclination of the mounting surface to the vertical surface is not more than ±5°;

● Impact and vibration: The product should be installed and used in places without significant shaking, impact, and vibration.

Structural Features   

● Modular design: Auxiliary contact groups, air delay heads, thermal relays, and other accessories are modularly designed and can be combined into various derivative products;

● Small size, low power consumption, long life, and reliable safety;

● It can be installed with screws or standard DIN rail.

 

Main Parameters and Technical Performance Indicators

Specifications TKDQ3-09 TKDQ3-12 TKDQ3-18 TKDQ3-25 TKDQ3-32 TKDQ3-40 TKDQ3-50 TKDQ3-65 TKDQ3-80 TKDQ3-95
Rated working current(A) 380V AC-3 9 12 18 25 32 40 50 65 80 95
AC-4 3.5 5 7.7 8.5 12 18.5 24 28 37 44
660V AC-3 7 9 12 18 27 34 39 42 49 49
AC-4 1.5 2 3.8 4.4 7.5 9 12 14 17.3 21.3
Rated heating current (A) 20 20 32 40 50 60 80 80 125 125
Rated insulation voltage (V) 690
Controllable three-phase squirrel-cage motor power (kW) AC-3 220V 2.2 3 4 5.5 7.5 11 15 18.5 22 25
380V 4 5.5 7.5 11 15 18.5 22 30 37 45
660V 5.5 7.5 10 15 18.5 30 33 37 45 55
Operating frequency (times/h) Loaded AC-3 1200 1200 1200 1200 600 600 600 600 600 600
AC-4 300 300 300 150 150 150 150 150 150 150
Unloaded 3600 3600 3600 3600 3600 3600 3600 3600 2400 2400
Electrical life (times) AC-3 1.0×10⁶ 0.8×10⁶ 0.6×10⁶
AC-4 0.2×10⁶ 0.15×10⁶ 0.1×10⁶
Mechanical life (times) 1.0×10⁷ 0.8×10⁷ 0.6×10⁷
Fuse model RT16-16 RT16-20 RT16-25 RT16-32 RT16-50 RT16-63 RT16-80 RT16-100 RT16-125
Operating coil Rated voltage Us (V) AC220、AC380
Operating voltage (V) Pick-up voltage: 85%~110%Us Release voltage: 20%~75%Us
Power consumption (VA) Pick-up 76 76 76 110 110 230 230 230 230 230
Holding 9.4 9.4 9.4 11 11 32 32 32 32 32
Specifications TKDQ3-115 TKDQ3-150 TKDQ3-170 TKDQ3-185 TKDQ3-205 TKDQ3-225 TKDQ3-245 TKDQ3-300 TKDQ3-330 TKDQ3-410 TKDQ3-475 TKDQ3-630
Rated working current(A) 380V AC-3 115 150 170 185 205 225 245 300 330 410 475 630
AC-4 50 65 70 75 80 90 100 124 130 150 185 225
660V AC-3 86 107 110 118 130 135 170 225 225 235 290 360
AC-4 25 32 35 35 40 40 47 60 60 72 85 100
Rated heating current (A) 250 250 250 275 275 315 315 400 400 450 580 800
Rated insulation voltage (V) 690 1000
Adjustable three-phase squirrel-cage motor power (kW) AC-3 380V 55 75 85 90 90 110 110 160 160 200 250 335
660V 80 90 100 110 110 129 129 220 220 280 330 450
Operating frequency (times/h) Loaded AC-3 600 600 600 300 300 300 300 300 300 300 300 300
AC-4 300 300 300 150 150 150 150 150 150 150 150 150
Unloaded 2400 2400 2400 2400 2400 2400 2400 2400 2400 1200 1200 1200
Electrical life (times) AC-3 0.4×10⁶ 0.5×10⁶ 0.3×10⁶
AC-4 0.2×10 5 1.0×10 5 0.8×10 5 0.5×10 5
Mechanical life (times) 0.3×10⁷ 0.1×10⁷
Fuse model RT16-160 RT16-200 RT16-250 RT16-315 RT16-400 RT16-500 RT16-630
Operating coil Rated voltage Us(V) AC220、AC380
Operating voltage(V) Pick-up voltage: 85%~110%Us Release voltage: 20%~75%Us
Power consumption
(VA)
Pick-up 300 300 300 800 800 800 800 1200 1200 1200 1250 1650
Holding 22 22 22 55 55 55 55 13 13 20 24 22