TKDB1E(L)-125 series IoT circuit breaker
Belonging Category:
Keywords:
TKDB1E(L)-125 series IoT circuit breaker
Product Details
Product Introduction
The TKDB1E(L) series Internet of Things circuit breaker (hereinafter referred to as "circuit breaker") is a new generation of product independently developed to meet the various requirements of the ubiquitous power Internet of Things for low-voltage power distribution. It integrates protection, measurement, remote control, communication, and fire warning monitoring functions. This circuit breaker is suitable for the control and isolation of low-voltage terminal power distribution. In addition to overload, short circuit, leakage, overvoltage, and undervoltage protection functions, it also has high-precision metering functions for electrical parameters such as current, voltage, power factor, and temperature. It can be applied to the system integration and connection of smart energy, smart homes, smart campuses, smart hotels, smart communities, and electrical fire safety supervision, realizing remote control, real-time alarm, statistical calculation, energy saving management, and big data analysis.
Standards Compliance
GB/T 14048.2 Low-voltage switchgear and controlgear - Part 2: Circuit-breakers
GB/T 16917.22 Household and similar general-purpose residual current operated circuit-breakers (RCBO) with overcurrent protection - Part 22: General rules for the applicability of RCBOs whose operating characteristics depend on the supply voltage
CQC 1148 Moulded-case circuit-breaker (MCCB) with remote control function
CQC 1149 Residual current operated circuit-breaker with overcurrent protection and remote control function
GB/T 32902 Residual current protective circuit-breaker (CBAR) with automatic reclosing function
Q/ZTT 2239 Technical Requirements and Inspection Standards for Differentiated Backup Power Equipment for Base Stations
Environmental Verification
GB/T 14597 Climatic environmental conditions for electrical products at different altitudes
GB/T 20645 Special environmental conditions - Technical requirements for low-voltage electrical appliances for plateau use
GB/T 2423.1 Environmental testing of electrical and electronic products - Part 2: Test methods - Test A: Low temperature
GB/T 2423.4 Environmental testing of electrical and electronic products - Part 2: Test methods - Test Db: Damp heat, cyclic (12h+12h cycle)
GB/T 2423.17 Environmental testing of electrical and electronic products - Part 2: Test methods - Test Kb: Salt mist
Stand working conditions
Ambient operating temperature: Normal -5℃~+40℃, Extreme -25℃~+70℃;
Installation altitude: Not exceeding 5000m (derating required for altitudes exceeding 2000m);
At a maximum temperature of +40℃, the relative humidity of the air shall not exceed 50%. At lower temperatures, higher relative humidity is permissible, e.g., 90% at 20℃. Special measures should be taken for condensation occasionally caused by temperature changes;
Pollution degree: Grade 3;
Circuit breaker protection level: IP20;
Usage category: A;
Installation category: Class Ⅲ;
Installation vertical inclination shall not exceed 5°;
Transportation and storage conditions: Not lower than -40℃, not higher than 70℃;
Model and Meaning
TKD 1 |
B 2 |
1 3 |
E 4 |
L 5 |
125 6 |
DC 7 |
C 8 |
80 9 |
2P 10 |
GSM 11 |
Serial Number | Description | Model Meaning |
---|---|---|
1 | Enterprise code | TKD: Shandong Taikai Electrical Appliance Co., Ltd. |
2 | Product Category | B: Miniature Circuit Breaker (MCB) |
3 | Design SN | 1 |
4 | Trip unit code | E: Electronic trip unit |
5 | Function code | L: With residual current protection (optional) |
6 | frame size | 125 |
7 | Product code | DC: DC circuit breaker, AC type without code |
8 | Trip type | Type C, Type D |
9 | Rated current (A) | 6, 10, 16, 20, 25, 32, 40, 50, 63, 80, 100, 125 |
10 | Pole number | 1P, 2P, 3P, 4P |
11 | Communication function | Standard RS-485, optional GSM, WIFI, Bluetooth |
Protection function and trip characteristics
TKDB1E-125 trip characteristics
Protection parameters | Set value |
---|---|
Overload long-delay current | Ir=6, 10, 16, 20, 25, 32, 40, 50, 63, 80, 100, 125A |
Overload long-delay time | tr=5~100s adjustable, step 1s |
Short-circuit instantaneous current | Ii=(4, 5, 6, 7, 8, 9, 10, 11, 12, 13, 14)xIr |
Short-circuit short-delay current | Isd=(2, 3, 4, 5, 6, 7, 8, 9, 10, 11, 12)xIr |
Short-circuit short-delay time | tsd=60~500ms adjustable, 1ms step |
Type | Test current | Time limit | Expected result | Notes |
---|---|---|---|---|
Overload long delay | 1.05Ir | t≤1h (In≤63A) | No tripping | Cold state |
t≤2h (In > 63A) | ||||
1.30Ir | t < 1h (In≤63A) | Tripping | Immediately after the test, the current increases steadily within 5 s | |
t < 2h (In > 63A) | ||||
Instantaneous short circuit | 8Ii | t≤0.2s | No tripping | Cold state, current is switched on by closing the auxiliary switch |
12Ii | t < 0.2s | Tripping | ||
Short-circuit short-delay | 0.8Isd | tsd±20% | No tripping | Cold state, current is switched on by closing the auxiliary switch |
1.2Isd | tsd±20% | Tripping |
Note: The reference calibration temperature of the circuit breaker is 30℃, and the temperature error is ±5 ℃.
TKDB1EL-125 tripping characteristics
Type | Test current | Time limit | Expected result | Notes |
---|---|---|---|---|
C, D | 1.13In | t≤1h (In≤63A) | No tripping | Cold state |
t≤2h (In > 63A) | ||||
1.45In | t < 1h (In≤63A) | Tripping | Immediately after the test, the current increases steadily within 5 s | |
t < 2h (In > 63A) | ||||
C, D | 2.55In | 1 s < t < 60 s (In≤32A) | Tripping | Cold state |
1 s < t < 120 s (In > 32A) | ||||
C | 5In | t≤0.1 s | No tripping | Cold state, current is switched on by closing the auxiliary switch |
D | 10In | |||
C | 10In | t < 0.1 s | Tripping | Cold state, current is switched on by closing the auxiliary switch |
D | 20In |
Note: The reference calibration temperature of the circuit breaker is 30℃, and the temperature error is ±5℃.
Main technical parameters
Item | TKDB1E-125 | TKDB1E-125DC | TKDB1EL-125 |
---|---|---|---|
Rated voltage(V) | AC230V, AC400V | DC12~72V | AC230V, AC400V |
Rated working current(A) | 6, 10, 16, 20, 25, 32, 40, 50, 63, 80, 100, 125 | ||
Pole number | 1P, 2P, 3P, 4P | 1P, 2P, 3P, 4P | 2P, 3P, 4P |
Rated residual operating current I Δn | / | / | 30, 50, 100, 300 (Without 30mA range with reclosing function) |
Rated residual non-operating current I Δno | / | / | 50%I Δn |
Rated insulation voltage Ui | 500V | 500V | 500V |
Rated impulse withstand voltage U imp | 4kV | 4kV | 4kV |
Closing time | ≤3s | ≤3s | ≤3s |
Opening time | ≤2s | ≤2s | ≤2s |
Automatic reclosing time | 20s~60s | 20s~60s | 20s~60s |
Rated ultimate breaking capacity Icu | 10kA | 15kA | / |
Rated operating breaking capacity Ics | 7.5kA | 15kA | Normal type 6kA, H type 10kA |
Rated short-circuit breaking capacity Icn | / | / | Normal type 6kA, H type 10kA |
Trip type | Electronic type | Electronic type | Type C, Type D |
Mechanical life | 20000 times | 20000 times | 20000 times |
Mechanical life | 4000 times | 4000 times | 4000 times |
Communication function | Standard RS-485, optional GSM, WIFI, Bluetooth | ||
Metering function | Monitoring of current, voltage, leakage current, power factor, etc., accuracy: 0.5 level or above |
Related Products
Product Inquiry
You can leave your opinions and suggestions here, and we will reply to you in time
SHANDONG TAIKAI ELECTRIC APPLIANCES CO., LTD.
Service Hotline:
86-538-8520889
Tel:
86-538-8520889(Sales and Marketing Support)
86-538-5366875(General Department, Human Resources Department)
Email:tkdgdq@163.com
Address: No.11 Leigushi East Street,Taishan District,TaiAnCity, Shandong Province

WeChat Official Account
copyright © 2025 ShanDong TaiKai Electric Appliances Co., Ltd.