TKDB1E(L)-125 series IoT circuit breaker

The TKDB1E(L) series Internet of Things circuit breaker (hereinafter referred to as "circuit breaker") is a new generation of product newly developed to meet the various requirements of the ubiquitous power Internet of Things for low-voltage power distribution. It integrates protection, measurement, remote control, communication, and fire prevention and early warning monitoring functions. This circuit breaker is suitable for the control and isolation of low-voltage terminal power distribution. In addition to overload, short circuit, leakage, overvoltage, and undervoltage protection functions, it also has high-precision metering functions for current, voltage, power factor, and temperature, etc. It can be applied to system integration and docking in smart energy, smart homes, smart campuses, smart hotels, smart communities, and electrical fire safety supervision, realizing remote control, real-time alarm, statistical calculation, energy saving management, and big data analysis.

Keywords:

TKDB1E(L)-125 series IoT circuit breaker

Product Details

Product Introduction

The TKDB1E(L) series Internet of Things circuit breaker (hereinafter referred to as "circuit breaker") is a new generation of product independently developed to meet the various requirements of the ubiquitous power Internet of Things for low-voltage power distribution. It integrates protection, measurement, remote control, communication, and fire warning monitoring functions. This circuit breaker is suitable for the control and isolation of low-voltage terminal power distribution. In addition to overload, short circuit, leakage, overvoltage, and undervoltage protection functions, it also has high-precision metering functions for electrical parameters such as current, voltage, power factor, and temperature. It can be applied to the system integration and connection of smart energy, smart homes, smart campuses, smart hotels, smart communities, and electrical fire safety supervision, realizing remote control, real-time alarm, statistical calculation, energy saving management, and big data analysis.

Standards Compliance

GB/T 14048.2 Low-voltage switchgear and controlgear - Part 2: Circuit-breakers

GB/T 16917.22 Household and similar general-purpose residual current operated circuit-breakers (RCBO) with overcurrent protection - Part 22: General rules for the applicability of RCBOs whose operating characteristics depend on the supply voltage

CQC 1148 Moulded-case circuit-breaker (MCCB) with remote control function

CQC 1149 Residual current operated circuit-breaker with overcurrent protection and remote control function

GB/T 32902 Residual current protective circuit-breaker (CBAR) with automatic reclosing function

Q/ZTT 2239 Technical Requirements and Inspection Standards for Differentiated Backup Power Equipment for Base Stations

Environmental Verification

GB/T 14597 Climatic environmental conditions for electrical products at different altitudes

GB/T 20645 Special environmental conditions - Technical requirements for low-voltage electrical appliances for plateau use

GB/T 2423.1 Environmental testing of electrical and electronic products - Part 2: Test methods - Test A: Low temperature

GB/T 2423.4 Environmental testing of electrical and electronic products - Part 2: Test methods - Test Db: Damp heat, cyclic (12h+12h cycle)

GB/T 2423.17 Environmental testing of electrical and electronic products - Part 2: Test methods - Test Kb: Salt mist

Stand working conditions

Ambient operating temperature: Normal -5℃~+40℃, Extreme -25℃~+70℃;

Installation altitude: Not exceeding 5000m (derating required for altitudes exceeding 2000m);

At a maximum temperature of +40℃, the relative humidity of the air shall not exceed 50%. At lower temperatures, higher relative humidity is permissible, e.g., 90% at 20℃. Special measures should be taken for condensation occasionally caused by temperature changes;

Pollution degree: Grade 3;

Circuit breaker protection level: IP20;

Usage category: A;

Installation category: Class Ⅲ;

Installation vertical inclination shall not exceed 5°;

Transportation and storage conditions: Not lower than -40℃, not higher than 70℃;

 

Model and Meaning

TKD  

1

B  

2

1 

3

E

4

L  

5

125 

6

DC  

7

C  

8

80 

9

2P 

10

GSM  

11

Serial Number Description Model Meaning
1 Enterprise code TKD: Shandong Taikai Electrical Appliance Co., Ltd.
2 Product Category B: Miniature Circuit Breaker (MCB)
3 Design SN 1
4 Trip unit code E: Electronic trip unit
5 Function code L: With residual current protection (optional)
6 frame size 125
7 Product code DC: DC circuit breaker, AC type without code
8 Trip type Type C, Type D
9 Rated current (A) 6, 10, 16, 20, 25, 32, 40, 50, 63, 80, 100, 125
10 Pole number 1P, 2P, 3P, 4P
11 Communication function Standard RS-485, optional GSM, WIFI, Bluetooth

Protection function and trip characteristics

TKDB1E-125 trip characteristics

Protection parameters Set value
Overload long-delay current Ir=6, 10, 16, 20, 25, 32, 40, 50, 63, 80, 100, 125A
Overload long-delay time tr=5~100s adjustable, step 1s
Short-circuit instantaneous current Ii=(4, 5, 6, 7, 8, 9, 10, 11, 12, 13, 14)xIr
Short-circuit short-delay current Isd=(2, 3, 4, 5, 6, 7, 8, 9, 10, 11, 12)xIr
Short-circuit short-delay time tsd=60~500ms adjustable, 1ms step
Type Test current Time limit Expected result Notes
Overload long delay 1.05Ir t≤1h (In≤63A) No tripping Cold state
t≤2h (In > 63A)
1.30Ir t < 1h (In≤63A) Tripping Immediately after the test, the current increases steadily within 5 s
t < 2h (In > 63A)
Instantaneous short circuit 8Ii t≤0.2s No tripping Cold state, current is switched on by closing the auxiliary switch
12Ii t < 0.2s Tripping
Short-circuit short-delay 0.8Isd tsd±20% No tripping Cold state, current is switched on by closing the auxiliary switch
1.2Isd tsd±20% Tripping

Note: The reference calibration temperature of the circuit breaker is 30℃, and the temperature error is ±5 ℃.

TKDB1EL-125 tripping characteristics   

Type Test current Time limit Expected result Notes
C, D 1.13In t≤1h (In≤63A) No tripping Cold state
t≤2h (In > 63A)
1.45In t < 1h (In≤63A) Tripping Immediately after the test, the current increases steadily within 5 s
t < 2h (In > 63A)
C, D 2.55In 1 s < t < 60 s (In≤32A) Tripping Cold state
1 s < t < 120 s (In > 32A)
C 5In t≤0.1 s No tripping Cold state, current is switched on by closing the auxiliary switch
D 10In
C 10In t < 0.1 s Tripping Cold state, current is switched on by closing the auxiliary switch
D 20In

Note: The reference calibration temperature of the circuit breaker is 30℃, and the temperature error is ±5℃.

Main technical parameters

Item TKDB1E-125 TKDB1E-125DC TKDB1EL-125
Rated voltage(V) AC230V, AC400V DC12~72V AC230V, AC400V
Rated working current(A) 6, 10, 16, 20, 25, 32, 40, 50, 63, 80, 100, 125
Pole number 1P, 2P, 3P, 4P 1P, 2P, 3P, 4P 2P, 3P, 4P
Rated residual operating current I Δn / / 30, 50, 100, 300
(Without 30mA range with reclosing function)
Rated residual non-operating current I Δno / / 50%I Δn
Rated insulation voltage Ui 500V 500V 500V
Rated impulse withstand voltage U imp 4kV 4kV 4kV
Closing time ≤3s ≤3s ≤3s
Opening time ≤2s ≤2s ≤2s
Automatic reclosing time 20s~60s 20s~60s 20s~60s
Rated ultimate breaking capacity Icu 10kA 15kA /
Rated operating breaking capacity Ics 7.5kA 15kA Normal type 6kA, H type 10kA
Rated short-circuit breaking capacity Icn / / Normal type 6kA, H type 10kA
Trip type Electronic type Electronic type Type C, Type D
Mechanical life 20000 times 20000 times 20000 times
Mechanical life 4000 times 4000 times 4000 times
Communication function Standard RS-485, optional GSM, WIFI, Bluetooth
Metering function Monitoring of current, voltage, leakage current, power factor, etc., accuracy: 0.5 level or above

Product Inquiry

You can leave your opinions and suggestions here, and we will reply to you in time